Approvals

31

6 - Technical specification

Features

(at 25°C enviromental temp.)

Setpoint

OP4 PV retransmission
(option)

One shot Fuzzy-Tuning
with automatic selection
Serial comm. (option)
Auxiliary Supply

Operational safety

General
characteristics

Description

Ramp up and down
Low limit
High limit

Galvanic isolation: 500 V

~

/1 min

Resolution 12bit (0.025%)
Accuracy: 0.1 %
The controller selects automatically the best
method according to the process conditions

Natural frequency

Step response

Current output: 0/4…20mA 750

/15V max

From low limit to the high range

From low range to the high limit

0.1…999.9 digit/min (Off = 0)

RS485 isolated, Modbus/Jbus protocol, 1200, 2400, 4800, 9600 bit/sec 2 wires

Electromagnetic
compatibility

Access protection

Power supply

Protection EN650529

Compliance to the CE standards for industrial system and equipment

Electric safety

IP20 termination unit
IP65 front panel

+18V– ±20%, 30mA max for an external transmitter supply

Password to access the configuration and parameters data

100 - 240V

~

(- 15% + 10%) 50/60Hz

or 24V

~

(- 25% + 12%) 50/60Hz and 24V– (- 15% + 25%)

Power consumption 1.6W max
Compliance to EN61010, installation class 2 (2500V) pollution class 2

Detection of out of range, short circuit or sensor break with automatic
activation of the safety strategies and alerts on display

Dimensions

Safety value: 0…+100%. (user enabled/disabled)
parameter and configuration data are stored in a non volatile memory for
an unlimited time

Measure input

1

/

32

DIN - 48 x 24, depth 120 mm, weight 100 gr. apx.

Control output

Parameters

UL, cUL

Advertising