28

5 - Automatic tune

5

AUTOMATIC

TUNE

Start/stop of the Fuzzy Tuning
The Tuning operation can be
started or stopped any time.

The green led

3 goes on when the

Fuzzy Tuning is in progress. At the
end of this operation, the calculat-
ed PID terms parameter are stored
and used by the control algorithm
and the controller goes back to the
operator mode. The green led

3

becomes off.
This function allows the calculation
of the optimal PID terms parame-
ters, monitoring the response of the
process to disturbances.
The controller provides 2 types of
“one shot” tuning algorithm, that are
selected automatically according to
the process condition when the
operation is started.

Step response
This type is selected when, at the
start of the autotune operation, the
PV is far from the Setpoint of more
than 5% of the span.
This method has the big advantage
of fast calculation, with a reasonable
accuracy in the term calculation.

Natural frequency
This type is selected when the PV is
close to the SP setpoint.

This method has the advantage of
a better accuracy in the term cal-
culation with a reasonable speed
calculation.
The Fuzzy Tuning determines
automatically the best method to
use to calculate the PID term,
according the process conditions.

274.8

tune

stop

strt

Operator

mode

press until

To start

select

strt

To stop

select

stop

Step response

SP

Natural frequency

Start of autotune

operation

PV variable

Control output

PV variable

Control output

tuning start

End of the tuning

operating and setting of

the new calculated

terms.

Setpoint change

End of the tuning

operating and setting of

the new calculated

terms.