4 - Operations

effectiveness of the PID algorithm.
Setting 1, the overshoot control is
disabled.

Control output
high limit

It specifies the maximum value the
control output can be set

Control output
hysteresis

Control output hysteresis span, set
in % of the full scale.

2nd GROUP

Setpoint
ramp up

Setpoint

ramp down

This parameter specifies the max-
imum rate of change of the Setpoint
in digit/min. When the parameter is
Off, this function is disabled.

#sl. d

#sl. u

Off

SP

On

Hysteresis of the threshold

hy

#hy.

#Op. H

Setpoint
low limit

Low limit of the setpoint value.
When the parameter is Off, this
function is disabled.

Setpoint
high limit

High limit of the setpoint value.
When the parameter is Off, this
function is disabled.

AL1
alarm hysteresis

AL2
alarm hysteresis

Hysteresis of the threshold of both
the alarms, that activate OP1 and
OP2 control output. It is specified
as a % of the full scale.

Input filter
time constant

Time constant, in seconds, of the RC
input filter applied to the PV input.
When this parameter is set to Off
the filter is bypassed.

#t.fil

#A2hy

#AIhy

#s.p. H

#s.p. l

Input shift

This value is added to the measured
PV input value. Its effect is to shift the
whole PV scale of up to ± 60 digits.

Controller
address

the address range is from 1 to 247
and must be unique for each con-
troller on the communication bus
to the supervisor.
When set to Off the controller is
not communicating

Retransmission
low range
Retransmission
high range

These parameters define the range
of the OP4 retransmission output.
Example: 4..20 mA output corre-
sponding to 20…120°C.

#rt.Hi

#rt.lo

#Addr

#In.sh

Filter response

100%

0

PV

63,2%

t.Fil

Time