6 - Technical specification

6

TECHNICAL SPECIFICATIONS

Common
characteristics

A/D converter with resolution of 50.000 points
Update measurement time: 0.2 seconds
Sampling time: 0.5 seconds
Input bias: - 60…+ 60 digit
Input filter with enable/disable: 1…30 seconds

Accuracy

0.25% ± 1 digits for temperature sensors
0.1% ±1 digits (for mV)
0.1% ±1 digits + accuracy of the used external
shunt resistor (for mA)

Between 100…240V

~

the error is minimal

Resistance
thermometer

Pt100

at 0°C

(IEC 751)

°C/°Fselectable

2 or 3 wires
connection

Max. wire Res.:
20

max (3 wires)

Input drift:
0.3°C/10°C Env.Temp.
<0.1°C / 10

Wire Res.

Thermocouple

L,J,T,K,S
(IEC 584)

°C/°F selectable

Internal cold junction
compensation
in °C/°F

Max. wire Res.:
150

max

Input drift:
<2µV/°C Env. Temp.
<0.5µV / 10

Wire Res.

DC input (current)

4…20mA,0-20mA
with external shunt 2.5

Rj >10M

Engineering units
Conf. decimal point position
Init. Sc. -999…9999
Full Sc. -999…9999
(min. range of 100 digits)

Input drift:
<0.1% / 20°C Env. temp.

DC input (voltage)

10…50mV, 0-50mV
Rj >10M

Features

(at 25°C enviromental temp.)

Total configurability
see

par. 3.2 pag. 16
par. 4.6 pag. 26

PV Input
(see pag.12 and pag. 16)

Description

From keypad or serial communication the user selects:
the type of input - the associated functions and the corresponding outputs - the type of control algo-
rithm - the type of output and the safe conditions - the type and functionality of the alarms
- the values of all the control parameters.