Athena Technologies PLATINUM C10 User Manual

Page 12

Advertising
background image

11

2 - Electrical connections

2.3.1 POWER SUPPLY

B

Switching power supply with mul-
tiple isolation and internal fuse
• Standard version:

nominal voltage:
100 - 240V

~

(- 15% + 10%)

Frequency 50/60Hz

• Low Voltage version:

Nominal voltage:
24V

~

(- 25% + 12%)

Frequency 50/60Hz
or 24V– (- 15% + 25%)

• Power consumption 1.6W max

0.2A included fuse

Supply

L

N

1

2

2.3.2 OP1 OUTPUT

B

2.3.3 OP2 OUTPUT

B

A] Single relay output
• NO contact for resistive load of

up to 2A / 250V

~

max.

• Fuse 2A

~

T

(IEC 127)

B] Triac Output
• NO contact for resistive load of

up to 1A / 250V

~

max.

• Fuse 1A

~

T

(IEC 127)

• Logic output, not isolated

0...5V–, ±20%, 30mA max

Varistor for
inductive loads
24V~ only

Fuse

Coil of the
load contactor

3

4

3

4

Varistor for
inductive loads
24V~ only

Fuse

Coil of the
load contactor

Load

Solid
state

relay

10

11

Advertising