4 - Operations

4.4 PARAMETER SETTING

A

The parameter setting procedure
has a timeout. If no keys are
pressed for, at least, 30 seconds,
the controller switches back, auto-
matically, to the operator mode.

After having selected the parame-
ter or the code, press

S and G

to display or modify the value (see
pag. 20) The value is entered when
the next parameter is selected, by
pressing the

R key.

Pressing the

Q key, the next

group of parameters is present-
ed on the display.

Values

modification

Modification/

selection

entry

Parameter

menù

selection

A2s.p

p.b.

t.i.

t.c.

t.d.

AIs.p

274.8

P

0

P

5:0

P

5:0

P

1:00

P

20

P

0

5000

OK

PASS

Back to the
Operator mode

Operator mode

1st GROUP

AL1 alarm threshold [1]
(see pag. 24)

AL2 alarm threshold [2]
(see pag. 24)

Proportional band
(PID algorithm only)
0.5…999.9% of span

Integral time
(PID algorithm only)

0ff

/ 0.0 ...100.0 min.

Derivative time
(PID algorithm only)

0ff

/ 0.01 ... 10.00 min.

Cycle time
(PID algorithm only)
1 ... 200 sec.

Note
[1]
It is presented only if the controller has been

configured with 2 alarms. Digit L of the con-
figuration code is assigned to 4 or 5

[2] It is not presented if the controller has been

configured with alarm n° 2 not active or of
sensor break type. Digit N of the configu-
ration code is assigned to 0 or 1.

[3] If password is 0000 to 4999, parameter set-

ting will be available to the operator with-
out entering this password number. If pass-
word is 5000 to 9999, parameter setting
will only be available by entering this pass-
word number.

Password entry [3]
only if

Code

value

5000

(see pages 26…27)

Code entry [3]
from 5000 to 9999
Must be equal to the
value of the parame-
ter

Code

YES