46-648 Jupiter Magnetostrictive Transmitters

The default password installed in the transmitter at the
factory is 0 (password disabled). The last step in the con-
figuration menu provides the option to enter a new pass-
word. If 0 is entered as a password, the transmitter is no
longer password protected and any value in the menu can
be altered (except diagnostic values) without entering a
confirming password.

NOTE: If the password is not known, the menu item New Password

displays an encrypted value representing the present pass-
word. Call the factory with this encrypted value to determine
the actual password.

1.6.4 Menu: Step-By-Step Procedure

The following table provides a complete explanation of
the software menus displayed by the Jupiter transmitter.
Use this table as a step-by-step guide to configure the
transmitter.

The first column presents the menus shown on the trans-
mitter display. The displays are in the order they would
appear if the arrow keys were used to scroll through the
menu. The numbers are not shown on the display. They
are provided as a reference.

The second column provides the actions to take when
configuring the transmitter. Additional information or an
explanation of an action is given in the third column.

Models with one float:
Level only calibration — proceed to Section 1.6.4.1
Interface only calibration — proceed to Section 1.6.4.2

Models with two floats:
Interface and level calibration — proceed to
Section 1.6.4.3

• The loop output will follow the interface layer.

• Upper liquid level is for display only.

Level and interface calibration — proceed to
Section 1.6.4.4

• The loop output will follow overall liquid level.

• Interface level is for display only.

NOTE: Float 1 is the float nearest to the transmitter head, Float 2 is

the second (i.e., for top-mounted units, Float 1 is the top level
float and Float 2 is the interface layer float; for bottom-mount-
ed models, Float 1 is the interface float, Float 2 is the top level
float).