6 configuring the transmitter, 1 operating parameters, 2 transmitter display and keypad – Orion Instruments Jupiter 2xx User Manual

Page 9: 3 password protection (default = 0)

Advertising
background image

46-648 Jupiter Magnetostrictive Transmitters

9

1.6

Configuring the Transmitter

The Jupiter transmitter comes configured from the factory
with regard to probe, float type, and orientation.

Information on configuring the transmitter using a HART
communicator is given in Configuration Using HART,
Section 1.7.

1.6.1 Operating Parameters

Some key information is needed to calibrate the Jupiter
transmitter. Complete the configuration information table.
See Configuration Information, Section 1.3.4.

1.6.2 Transmitter Display and Keypad

The Jupiter transmitter has a liquid-crystal display (LCD)
capable of showing two lines of 8 characters each.
Transmitter measurements and configuration menu screens
are shown on the LCD.

The transmitter default display is the measurement screen.
It cycles every 5 seconds to display STATUS, LEVEL,
%OUTPUT, and LOOP information. The transmitter
defaults to this display after 5 minutes if no keystrokes
are sensed.

The keypad has three arrows used to scroll through the
displays and to calibrate the transmitter – the Up and
Down Arrow (

) keys and the Enter (

) key.

1.6.3 Password Protection (Default = 0)

The Jupiter transmitter is password protected to restrict
access to certain portions of the menu structure that affect
the operation of the system. When the proper password is
entered, an exclamation point (!) appears as the last charac-
ter of the first line of the display. The password can be
changed to any numerical value up to 255. The password
is required whenever configuration values are changed.

Б

Б

Б

Function in

Function in

Arrows

Display Mode

Configuration Mode

Up and Down Moves forward and backward

Increases or decreases the

in the configuration program

value displayed or moves to

from one display to another.

another choice.

Note: Hold arrow key for
rapid scrolling.

Enter

Enters the configuration mode

Accepts a value and returns

(noted by an exclamation point to the display mode.
as the last character in the top
display line).

Б

Б

Б