2 status messages – Orion Instruments Jupiter 2xx User Manual

Page 26

Advertising
background image

26

46-648 Jupiter Magnetostrictive Transmitters

2.3.2

Status Messages

Display Message

Action

Comment

OK

None

Normal operating mode

Initial

None

Shown at power-up during
self check

TrimReqd

Factory set Loop values are defaults,

Consult Factory

loop output may be in accurate

Cal Reqd

Factory set default calibration parameters

Consult Factory

are in use, level reading may be inaccurate

Lo Temp

Present temperature in electronics

Transmitter may need to be moved

compartment is below -40° F (-40° C)

to ensure temperature is within
specification

Hi Temp

Present temperature in electronics

Transmitter may need to be moved

compartment is above +176° F (+80° C)

to ensure temperature is within
specification

Float 2

No level signal detected from float 2

Make sure 2 floats are being used,

Fail

are not damaged, and within
measuring range

Float 1

No level signal detected from float 1

Make sure float is not damaged

Fail

and within measurement range

No Signal

No signal detected from any float

Make sure float is not damaged
and within measurement range

LoopFail

Loop current differs from expected value

Consult Factory

Snsr Brd

Measurement board not responding

Consult Factory

DfltParm

Internal non-volatile parameters have been

Consult Factory

reset to default values