3 troubleshooting flowchart – Orion Instruments Jupiter 2xx User Manual

Page 27

Advertising
background image

46-648 Jupiter Magnetostrictive Transmitters

27

Unit Equipped

with Display?

Check Voltage at

Terminal Board

No Voltage?

Check Power

Supply and Wiring

Negative
Voltage?

Reverse Wiring

Consult Factory

Check Loop

Current at terminal

Board

Loop Current

Above 23 mA?

Remove Electronic

Module

Loop Current

Above 1 mA?

Replace Terminal

Board

Replace Electronic

Module

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

No

No

Display has

Text?

No

Reseat Boards.

Check Power

Supply and Wiring

Loop

Resistance

Wrong?

Correct Loop

Resistance

Start

Good

Display

No

Active

HART

Yes

Failure to Operate

with Correct Loop

Inputs

No

Faint Display?

Yes

Yes

No

Some problems could be

temporarily solved by power
cycling the unit. Please call

factory if this problem persists.

Display

Working?

No

Yes

No

Retest

Yes

HART

Communications

OK?

Voltage Above

36 Volts?

Voltage

< 12V

2

1

3

2.3.3

Troubleshooting Flowchart