1 measurement type: level only – Orion Instruments Jupiter 2xx User Manual

Page 11

Advertising
background image

46-648 Jupiter Magnetostrictive Transmitters

11

1.6.4.1 Measurement Type: Level Only

Display

Action

Comment

1

Status
Level
% Output
Loop

Transmitter Display

Transmitter default display. Status, Level, % Output, and Loop
values cycle every 8 seconds.

2

Level

xxx.xx

Transmitter Display

Level measurement in centimeters or inches

3

% Output

xx.xx%

Transmitter Display

Level as a percentage of loop current span

4

Loop

xx.xx mA

Transmitter Display

Loop current output (mA)

5

MeasType

Select type of measurement

Choose Lvl Only

6

Units

Select units of length

Choose cm or in

7

Probe Ln
xxx.xxlu

Enter exact length of probe

6–420 inches (15.24–1066.8 cm)

8

Set 4mA

xxx.xxlu

Enter the PV value for 4 mA
point

Enter 4 mA point in level units

9

Set 20mA
xxx.xxlu

Enter the PV value for 20 mA
point

Enter 20 mA point in level units

10

Lvl Ofst
xxx.xxlu

Enter the level offset value

Changes zero level as referenced from probe tip

11

Damping

xx.x s

Enter damping filter time

0–1 second in 0.1 increments
1–25 seconds in 1.0 increments

12

Fault

22mA

Select loop current under
fault condition

3.6 mA, 22 mA or Hold

13

Poll Adr

xx

Enter HART polling address
number

0–15

14

Trim 4

xxxx

Adjust 4 mA point

Attach a meter to the output. If the output does not equal 4 mA,
adjust the value of the display until the meter reads 4 mA

15

Trim 20

xxxx

Adjust 20 mA point

Attach a meter to the output. If the output does not equal 20 mA,
adjust the value of the display until the meter reads 20 mA

16

Loop Tst

Enter a mA value

Set mA output to a value between 3.6 and 22.0 mA

17

DeadBand

xx.x

Factory Setting

Diagnostic, factory setting

18

Snsr Mnt

Enter mounting type

MLI Top (external probe; transmitter top mounted)
MLI Bot (external probe; transmitter bottom mounted)
Dir Near (NPT, BSP, and 600# or less flanged probe)
Dir Ext (flanged probes 900# class and over)

19

Trim Lvl

xx.xx

Enter value to adjust Level
reading

-20.00 inches

≤ Trim Lvl ≤ 20.00 inches

20

F1 Cnts

Display only

For factory diagnostic use

21

New Pass

Xxx

Enter new password

Use up and down keys to select desired value (0–255)

22

Language
(select)

Select from English or
Spanish

Changes display language

23

Jupiter HT

Ver 3.0A

Display only

Product firmware version

Advertising