I/o menu descriptions, continued – Fairbanks 2800 Series Intrinsically Safe Instrument User Manual

Page 41

Advertising
background image

Section 3: Programming

01/12

41

50647 Rev. 9

3.5.1. I/O MENU DESCRIPTIONS, CONTINUED

PROMPT

COMMENT(S)

LoSEt

 Sets the weight value associated with 4mA.
 Usually

"

0

".

1. At

the

LoSEt

prompt, press

ENTER

.

2. Use the numeric keypad to enter desired weight value.
3. Press

ENTER

.

hiSEt

 Associated weight value of 20MA.
 Usually the capacity of the scale.
1. Press

ENTER

at the

hiSEt

prompt.

2. Use the numeric keypad to enter the desired weight value.
3. Press

ENTER

.

4 AdJ

Press

ENTER

to display a current number representing the 4mA Output.

─ See note on key functions.

20 AdJ

Press

ENTER

to display a current number representing the 20mA

Output.

─ See note on key functions.

AgtESt

LP4

- TO -

LP22

.

Press

ENTER

to perform an analog test.

4mA thru 22mA will be output momentarily in 2mA steps.
When adjusting either 4mA or 20mA, the following numeric keys increase
or decrease the reference value in the fashion that follows.

Increased by:

Decreased by:

9

10,000

4

10,000

8

1,000

3

1,000

7

100

2

100

6

10

1

10

5

1

0

1

ConoPt

Used for Continuous Output.
Choices include the following:

3052r

FbStd

FbPUtr

troniC

ConCon

ProtoA

Protocol setting for Port A choices include selections for the following:

bAUd 9600, 600

,

1200

,

2400

, and

4800

ChAr 8

and

7

PAritY nonE

,

odd

, and

EuEn

Advertising