Operating Instructions – Automatic

The automatic function allows a user to program an automatic recovery, vacuum, leak test, and /

or charge sequence. The user may choose to skip any step in the automatic operation during the

programming. A total automatic sequence may take an hour to complete.
Note: When a charge cycle in automatic mode is complete, the machine will not prompt to equalize

hoses; it will automatically compensate this amount of refrigerant.
1. Connect the high- and low-side service hoses to the A/C system; open the coupler valves on the hoses.
2. Select AUTOMATIC.
3. Decide if the unit should collect pre-recovery diagnostics by selecting YES or NO. Note: Data

may be printed from the Recover Diagnostics screen.

4. Decide if the unit should perform a recovery by selecting YES or NO. Note: Selecting YES

automatically programs the vacuum step of the recovery process. Selecting NO disables recovery,

but vacuum remains a choice for the operator. The next step would be to set vacuum time.

Operating Tips

• If the weight entered is more than the refrigerant

available in the internal tank, the charge

function will not start. The display reads

INSUFFICIENT REFRIGERANT

THERE IS NOT ENOUGH REFRIGERANT IN

THE ISV TO COMPLETE CHARGE. PRESS

TANK FILL TO ADD MORE OR EXIT TO ABORT.

Refer to the Maintenance section of this manual

for instructions to Manually Fill the ISV.

If problems are encountered during the

automatic sequence, the unit will “beep” three

times and the control panel readout will pinpoint

the problem encountered. The sequence

remains paused until the user enters a decision

regarding how to proceed.

Before the unit begins evacuating the A/C

system during the automatic sequence, it

checks for any pressure in the system that

may damage the vacuum pump. If pressure is

detected, the unit displays

PRESSURE TOO HIGH FOR VACUUM!

PRESS EXIT

Select EXIT. Recover refrigerant before

proceeding.

If a leak test was programmed, and a leak is

detected, the unit displays

LEAK TEST FAILED

CONTINUE WITH AUTOMATIC MODE?

PRESS YES TO CONTINUE NO TO ABORT.

Select NO to exit automatic sequence and

perform needed repairs. Press YES to continue

automatic sequence despite the failed leak test.

To ensure an accurate leak test, it is imperative

that a thorough recovery and evacuation of

the system is performed. During the recovery

process, cold spots can develop in the A/C

system. Pockets of refrigerant in desiccant and

in system oil will continue to vaporize as the A/C

system temperature equalizes toward ambient.

As this occurs, A/C system pressure increases,

which may be interpreted by the unit as a leak.

This varies somewhat with ambient temperature

conditions.

5. Decide if the unit should perform a leak test by

selecting YES or NO.

6. Decide if the unit should perform a charge by

selecting YES or NO. If yes, enter amount of oil to

be injected.

Note: The amount of oil recovered during the

recovery cycle is automatically injected before

the charge cycle, and no entry will be necessary.

If recovery was not selected, the amount of oil to

be injected may be entered while programming

the charge information.

7. Toggle DYE INJECT on or off. Select SAVE to

return to the charge screen.

8. Select MODE to toggle between high- or low-side

charge, or both. Note: Charge mode after injecting

oil allows only a high-side charge. Enter a charge

weight using the keypad, and select SAVE.

9. The display shows an overview of all tests

selected. Select START to begin the automatic

sequence.

10.When the sequence is complete, the display shows

CHARGE DIAGNOSTICS (if applicable)

START A/C TO PERFORM DIAGNOSTICS OR

WITH A/C OFF PRESS NEXT TO CLEAR

HOSES.

To obtain current pressure readings and

diagnostics from the vehicle, start the vehicle's air

conditioning system, or select NEXT to continue.

11. Close the high- and low-side coupler valves, and

remove the service hoses from the A/C system.

12. Select NEXT to begin clearing hoses. This

prepares the machine for the next service.

13. The machine displays a summary of actions

performed during the automatic sequence.