22

Maintenance

4. The display reads

CAREFULLY REMOVE USED FILTER AND

INSTALL NEW FILTER.

SELECT EXIT TO FINISH

Open the rear door of the unit and unscrew the

old filter. See Figure 12.

5. Look at the new filter—verify both o-rings are

lubricated and correctly located in the grooves.
See Figure 13. Thread the new filter into place
and tighten.

6. Close the rear door. Select EXIT. The filter-drier

replacement is complete.

Replace the Filter-Drier contd .

Filter-

Drier

Figure 12

rear view without shroud

Scale Calibration Check

The calibration check is used to ensure the unit’s

internal scale is always calibrated. During this test,

use only the calibration weight that is provided with

the unit.
1. Select SETUP MENU. Scroll to CALIBRATION

CHECK and select START.

2. The unit displays

MAKE SURE NOTHING IS ATTACHED TO THE

TEST MAGNET UNDERNEATH THE UNIT.

PRESS START TO BEGIN OR EXIT TO

ABORT.

Refer to Figure 14, and verify the magnet on the

bottom of the unit is clean. Select START.

3. The unit displays

INSTALL STEEL CALIBRATION BALL ONTO

MAGNET UNDERNEATH UNIT. PRESS NEXT

TO CONTINUE OR EXIT TO ABORT.

Attach the weight provided to the magnet on the

bottom of the unit. Select NEXT.

• If the display shows

CALIBRATION CHECK PASSED

PRESS EXIT TO CONTINUE

the scale is in calibration. Select EXIT.
• If the display shows CALIBRATION CHECK

FAIL, the scale is out of calibration. Contact

an authorized Robinair service center for
assistance.

Magnet

Figure 14

O-rings

Figure 13