5. I/O Signal Control and Signal Functions

z PIO pattern = 2 [256-point mode (256-point type)]

Category Signal

name

Signal

abbreviation

Function overview

PC1
PC2
PC4
PC8
PC16
PC32
PC64

Command position
number

PC128

The target position number is input.
A command position number must be specified by 6 ms before
the start signal (CSTR) turns ON.

Brake release

BKRL

This signal is used on an actuator equipped with a brake to
forcibly release the brake.

Operating mode

RMOD

This signal switches the operating mode between AUTO and
MANU.

Home return

HOME

Home return operation is started at a rise edge of this signal.

*Pause *STP

ON: Actuator can be moved, OFF: Actuator decelerates to a
stop

Start

CSTR

The actuator will start moving at a rise edge of this signal.

Alarm reset

RES

An alarm is reset at a rise edge of this signal.

Input

Servo ON

SON

The servo remains ON while this signal is ON.
The servo remains OFF while this signal is OFF.

PM1
PM2
PM4
PM8
PM16
PM32
PM64

Completed position
number

PM128

The relevant position number is output when positioning has
completed.
The signal will turn OFF when the next start signal is received.
It is used by the PLC to check if the commanded position has
definitively been reached, and also to provide a position
interlock, etc.

Position zone

PZONE

This signal becomes effective after a position movement
command is input. It will turn ON when the current actuator
position enters the range specified in the position table and
remain ON until the actuator exits the range.

Operating mode status RMDS

This signal will remain OFF during the AUTO mode, and ON
during the MANU mode.

Home return
completion

HEND

This signal is OFF immediately after the power is input, and
turns ON when home return has completed.

Position complete

PEND

This signal turns ON when the target position was reached
and the actuator has entered the specified in-position range.
It is used to determine whether positioning has completed.

Ready SV

This signal is always output once the servo is turned ON and
the controller is ready to operate.

*Emergency stop

*EMGS

OFF: Emergency stop has been actuated

Output

*Alarm *ALM

This signal remains ON in normal conditions of use and turns
OFF when an alarm generates.