Holding registers (cont’d), Device status – System Sensor FAAST Modbus User Manual

Page 10

Advertising
background image

User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1

10

Holding Registers (Cont’d)

Device Status

Address

Size
(16-bit
words)

Parameter Name

Type

Description

8

½

Relay Status

U8

Relay Status.

Bit 0:

Alert

Bit 1:

Action1

Bit 2:

Action2

Bit 3:

Fire1

Bit 4:

Fire2

Bit 5:

Minor (if equipped)

Bit 6:

Urgent/Fault

Bit7:

Isolate (if equipped)

Bits 8-15 unused

9

1

Internal Error Flags – HW Comm

U16

Internal Comm Error.

For internal use only.

10

1

Internal Error Flags – HW

U16

Internal HW Error.

For internal use only.

11

1

Internal Error Flags – SW

U16

Internal SW Error.

For internal use only.

12

1

Fan Speed in RPMs

U16

Speed of fan in RPMs

13

½

Alarm Level

U8

Alarm Status.

Bit 0:

Alert

Bit 1:

Action1

Bit 2:

Action2

Bit 3:

Fire1

Bit 4:

Fire2

Bits 5-15 unused.

14

1

Lifetime Count in Days

U16

Days of operation during lifetime

15

½

Filter Cover State

U8

Filter Cover State.

Not zero =

open

0 =

closed

16

1

Factory Configuration Status

U16

Factory Configuration State.

CONFIG_STATE_PRIMARY

0,

CONFIG_STATE_BACKUP

1,

CONFIG_STATE_UNCONFIGURED 2

17

1

Device Configuration Status

U16

Device Configuration State.

See Factory Configuration State.

18

1

Network Configuration Status

U16

Network Configuration State.

See Factory Configuration State.

19-30

12

Password Recovery Code

U16

Code for recovering the device PipeIQ password.

Uses the format to store a string.

Table 3.

Device Status Modbus Holding Registers