User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1

16

Device Configuration (Cont’d)

Address

Size
(16-bit
words)

Parameter Name

Type

Description

372-373

2

Fire2 Night Threshold

F32

Fire2 Alarm Night Obscuration Threshold

374-375

2

Fire2 Weekend Threshold

F32

Fire2 Alarm Weekend Obscuration Threshold

376-377

2

Alert Acclimate Threshold Max

F32

Maximum Alert Alarm Threshold when operating in

Acclimate

®

Mode

378-379

2

Alert Acclimate Threshold Min

F32

Minimum Alert Alarm Threshold when operating in

Acclimate Mode

380-381

2

Action1 Acclimate Threshold Max

F32

Maximum Action1 Alarm Threshold when operating in

Acclimate Mode

382-383

2

Action1 Acclimate Threshold Min

F32

Minimum Action1 Alarm Threshold when operating in

Acclimate Mode

384-385

2

Action2 Acclimate Threshold Max

F32

Maximum Action2 Alarm Threshold when operating in

Acclimate Mode

386-387

2

Action2 Acclimate Threshold Min

F32

Minimum Action2 Alarm Threshold when operating in

Acclimate Mode

388-389

2

Fire1 Acclimate Threshold Max

F32

Maximum Fire1 Alarm Threshold when operating in

Acclimate Mode

390-391

2

Fire1 Acclimate Threshold Min

F32

Minimum Fire1 Alarm Threshold when operating in

Acclimate Mode

392-393

2

Fire2 Acclimate Threshold Max

F32

Maximum Fire2 Alarm Threshold when operating in

Acclimate Mode

394-395

2

Fire2 Acclimate Threshold Min

F32

Minimum Fire2 Alarm Threshold when operating in

Acclimate Mode

396

½

ID Number

U8

Can be used for the SLC address or an identification

number on a loop

Flashscan 1-Address:

1-159

Flashscan 5-Address:

1-155

CLIP:

1-99

397-428

32

Contact

U8[64]

UTF-16 Contact Name string buffer

431-460

32

Facility

U8[64]

UTF-16 Facility Name string buffer

461-492

32

Facility Location

U8[64]

UTF-16 Facility Location string buffer

493-524

32

Device Location

U8[64]

UTF-16 Device Location string buffer

525-527

3

Button Lock

U8[3]

User Interface Lockout

Unlocked 0

Locked

1

Bit 0:

Isolate

Bit 1:

Reset/Mode

Bit 2:

Test

528-529

2

Passcode

U32

Passcode for unlocking the buttons from the front panel.

Unsigned Long Value: 1111-9999

Table 7.

Device Configuration Modbus Holding Registers

Warning!! Device threshold configuration variables should be set by the user to values scaled based on the Units configuration

setting. The detector will interpret the value differently for different Units settings. E.g. The device will interpret a 0.01 threshold

setting as 0.01 %/ft when Units setting is US Standard. The device will interpret a 0.01 threshold setting as 0.01 %/m when Units

setting is Metric.