User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1

18

Appendix A. Configurable options on FAAST

A.1. Alarm Configuration Variables

Name

Description

Range

Default Value

Units

AlertThresholdDay

The sensitivity where the Alert Alarm will occur during the daytime.

0.00046 – 6.25

0.0015 – 20.5

0.012

0.0396

%/ft %/m

Action1ThresholdDay

The sensitivity where the Action1 Alarm will occur during the

daytime.

0.00046 – 6.25

0.0015 – 20.5

0.05

0.165

%/ft %/m

Action2ThresholdDay

The sensitivity where the Action2 Alarm will occur during the

daytime.

0.00046 – 6.25

0.0015 – 20.5

0.1

0.33

%/ft %/m

Fire1ThresholdDay

The sensitivity where the Fire1 Alarm will occur during the daytime.

0.00046 – 6.25

0.0015 – 20.5

0.25

0.825

%/ft %/m

Fire2ThrehsoldDay

The sensitivity where the Fire2 Alarm will occur during the daytime.

0.00046 – 6.25

0.0015 – 20.5

0.5

1.65

%/ft %/m

AlertThresholdNight

The sensitivity where the Alert Alarm will occur during the nighttime.

0.00046 – 6.25

0.0015 – 20.5

0.012

0.0396

%/ft %/m

Action1ThresholdNight

The sensitivity where the Action1 Alarm will occur during the

nighttime.

0.00046 – 6.25

0.0015 – 20.5

0.05

0.165

%/ft %/m

Action2ThresholdNight

The sensitivity where the Action2 Alarm will occur during the

nighttime.

0.00046 – 6.25

0.0015 – 20.5

0.1

0.33

%/ft %/m

Fire1ThresholdNight

The sensitivity where the Fire1 Alarm will occur during the

nighttime.

0.00046 – 6.25

0.0015 – 20.5

0.25

0.825

%/ft %/m

Fire2ThrehsoldNight

The sensitivity where the Fire2 Alarm will occur during the

nighttime.

0.00046 – 6.25

0.0015 – 20.5

0.5

1.65

%/ft %/m

NightTimeEnter

Time at which to switch to nighttime thresholds.

10:00pm

Time

NightTimeExit

Time at which to switch to daytime thresholds.

5:00am

Time

AlertHigh

Sensitive limit for Alert when acclimate mode is active

0.00046 – 6.25

0.0015 – 20.5

0.00138

0.00455

%/ft %/m

Action1High

Sensitive limit for Action1 when acclimate mode is active

0.00046 – 6.25

0.0015 – 20.5

0.0028

0.00924

%/ft %/m

Action2High

Sensitive limit for Action2 when acclimate mode is active

0.00046 – 6.25

0.0015 – 20.5

0.0075

0.02475

%/ft %/m

Fire1High

Sensitive limit for Fire1 when acclimate mode is active

0.00046 – 6.25

0.0015 – 20.5

0.01

0.033

%/ft %/m

Fire2High

Sensitive limit for Fire2 when acclimate mode is active

0.00046 – 6.25

0.0015 – 20.5

0.1

0.33

%/ft %/m

AlertLow

Insensitive limit for Alert when acclimate mode is active

0.00046 – 6.25

0.0015 – 20.5

0.012

0.0396

%/ft %/m

Action1Low

Insensitive limit for Action1 when acclimate mode is active

0.00046 – 6.25

0.0015 – 20.5

0.05

.165

%/ft %/m

Action2Low

Insensitive limit for Action2 when acclimate mode is active

0.00046 – 6.25

0.0015 – 20.5

0.1

0.33

%/ft %/m

Fire1Low

Insensitive limit for Fire1 when acclimate mode is active

0.00046 – 6.25

0.0015 – 20.5

0.25

0.825

%/ft %/m

Fire2Low

Insensitive limit for Fire2 when acclimate mode is active

0.00046 – 6.25

0.0015 – 20.5

0.5

1.65

%/ft %/m

AcclimateAlertLevel

Current Sensitivity for Alert Alarm when in acclimate mode.

AlertHigh –

AlertLow

AlertLow

%/ft %/m

AcclimateAction1Level

Current Sensitivity for Action1 Alarm when in acclimate mode.

Action1High –

Action1Low

Action1Low

%/ft %/m

AcclimateAction2Level

Current Sensitivity for Action2 Alarm when in acclimate mode.

Action2High –

Action2Low

Action2Low

%/f %/m

AcclimateFire1Level

Current Sensitivity for Fire1 Alarm when in acclimate mode.

Fire1High – Fire-

1Low

Fire1Low

%/ft %/m

AcclimateFire2Level

Current Sensitivity for Fire2 Alarm when in acclimate mode.

Fire2High – Fire-

2Low

Fire2Low

%/ft %/m

Table 9.

Alarm Configuration Variable Ranges