User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1

9

Rev A0

Holding Registers

Note: The Modbus Holding Register addresses are indexed for a Honeywell Building Solutions Enterprise Building Integrator

TM

client.

Other clients may need to subtract 1 from each address in order to access the desired register.

Device Status

The device’s Device Status Structure is READ ONLY and mapped directly to a set of holding registers. The structure in the Firmware

is defined as follows:

Address

Size
(16-bit
words)

Parameter Name

Type

Description

40001-2

2

Universal Time Stamp

U32

Read Only - Universal Time Stamp corresponding to the

real-time clock value in UNIX seconds epoch format

3

1

Startup Flags

U16

Startup flags

For internal use only.

4

1

System Faults

U16

System Faults.

Bit 0:

Low Voltage

Bit 1:

Low Flow

Bit 2:

Configuration

Bit 3:

Sensor

Bit 4:

External Monitor

Bit 5:

Time

Bit 6:

Communication

Bit 7:

Aspirator

Bit 8:

Filter

Bit 9:

Isolation

Bit 10: High Flow

Bits 11-15 unused

5

1

Minor Faults

U16

Minor Faults.

Bit 0:

Low Flow

Bit 1:

Configuration

Bit 2:

External Monitor Open

Bit 3:

External Monitor Short

Bit 4:

Time

Bit 5:

Filter

Bit 6:

High Flow

Bits 7-15 unused

6

1

Urgent Faults

U16

Urgent Faults.

Bit 0:

Low Flow

Bit 1:

Configuration

Bit 2:

Communication

Bit 3:

Sensor

Bit 4:

Aspirator

Bit 5:

Filter

Bit 6:

High Flow

Bit 7:

Low Voltage

Bits 8-15 unused

7

1

Operating Mode

U16

Device Operating Mode Enumeration:

CONFIGURATION_MODE 0,

INITIALIZATION_MODE 1,

TEST_MODE

2,

NORMAL_MODE

3,

DISABLE_MODE

4,

RESET_MODE

5,

FACTORY_MODE

6,

SERVICE_MODE

7,

ISOLATE_NEW_MODE 8,

RESET_NETWORK_MODE 9