A.2. device configuration variables – System Sensor FAAST Modbus User Manual

Page 19

Advertising
background image

User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1

19

Rev A0

A.2. Device Configuration Variables

Name

Description

Range

Default Value

Acclimate Mode Enable

Set to activate acclimate mode operation

Enable / Disable

Disabled

Alert Alarm Latch

Set to latch Alert alarm. Requires a RESET to clear

alarm. This setting is only valid for conventional

product.

Latching/Non-Latching

Latching

Action1 Alarm Latch

Set to latch Action1 alarm. Requires a RESET to

clear alarm. This setting is only valid for conventional

product.

Latching/Non-Latching

Latching

Action2 Alarm Latch

Set to latch Action2 alarm. Requires a RESET to

clear alarm. This setting is only valid for conventional

product.

Latching/Non-Latching

Latching

Fire1 Alarm Latch

Set to latch Fire1 alarm. Requires a RESET to clear

alarm. This setting is only valid for conventional

product.

Latching/Non-Latching

Latching

Fire2 Alarm Latch

Set to latch Fire2 alarm. Requires a RESET to clear

alarm. This setting is only valid for conventional

product.

Latching/Non-Latching

Latching

Alert Delay

Programmable delay before activating Alert Alarm.

This setting is only valid for conventional product.

0 - 60 seconds

0

Action1 Delay

Programmable delay before activating Action1

Alarm. This setting is only valid for conventional

product.

0 - 60 seconds

0

Action2 Delay

Programmable delay before activating Action2

Alarm. This setting is only valid for conventional

product.

0 - 60 seconds

0

Fire1 Delay

Programmable delay before activating Fire1 Alarm.

This setting is only valid for conventional product.

0 - 60 seconds

0

Fire2 Delay

Programmable delay before activating Fire2 Alarm.

This setting is only valid for conventional product.

0 - 60 seconds

0

PassCodeButtonLockout

Allows lockout feature of buttons.

0000 - 9999

1111

TEST Lockout

Setting for locking and unlocking of TEST button.

This setting is only valid for conventional product.

Locked / Unlocked For the lock

function to work the passcode

must be any value other than

0000

Locked

RESET Lockout

Setting for locking and unlocking of RESET button.

This setting is only valid for conventional product.

Locked

DISABLE Lockout

Setting for locking and unlocking of DISABLE button.

This setting is only valid for conventional product.

Locked

IP Address

IP address of the device

192.168.1.10

Subnet Mask

255.255.255.0

Gateway

192.168.1.1

Address

Device local address range

CLIP enabled product

Flashscan enabled product

Eclipse enabled product

0-255

1-99

1-159

1-255

1

Time

Real time clock time in hours/minutes/seconds

Midnight

Date

Real time clock date

Current date

Year

Real time clock year

Current year

Log Setting

Configures the method of Event logging for either

FIFO (first in first out) or LIFO (last in first out) setting

FIFO / LIFO

FIFO

Password User

Password for Web Access User entry

Monitor

Table 10.

Device Configuration Variable Ranges.