Modbus configuration, Input registers – System Sensor FAAST Modbus User Manual

Page 8

Advertising
background image

User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1

8

Modbus Configuration

The device’s Modbus Configuration Structure is READ/WRITE and mapped directly to a set of holding registers. The structure in the

Firmware is defined as follows:

Address

Size
(16-bit
words)

Parameter Name

Type

Description

40326

1

Administrator Password

U16

Password to enable Commands through the Command

holding register.

Enter as an Unsigned Decimal number.

327

1

Sensor Command Register

U16

Command Register:

0xAA11 – Save Configuration

0xEE22 – Save Time

328

1

Event Log Index

U16

Starting Index of Event Log Entry which to read

329

1

Trend Log Index

U16

Starting Index of Trend Log to read

330

1

Message Log Index

U16

Starting Index of Message Log to read

Table 1.

Modbus Specific configuration Holding Registers

Information - Registers 326-330 can be configured by using Function code 6(single write) or Function 16 (multiple write).

Input Registers

The Modbus Holding Register addresses are indexed for a Honeywell Building Solutions Enterprise Building Integrator

TM

client. Other

clients may need to subtract 1 from each address in order to access the desired register.

Address

Size
(16-bit
words)

Parameter Name

Type

Description

30001

1

Schema

U16

Modbus Firmware Schema for client to determine version of

register mapping.

Table 2.

Modbus Input Registers

Advertising