Device configuration – System Sensor FAAST Modbus User Manual

Page 15

Advertising
background image

User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1

15

Rev A0

Device Configuration

Address

Size
(16-bit
words)

Parameter Name

Type

Description

40331

1

Device Config Counter

U16

Configuration Counter

332-333

2

Config Timestamp

U32

Time of last configuration

334

1

Units

U16

Units of Measure for Alarm Threshold Obscuration Values

Metric 0

US Standard 1

335

½

Relays Latching

U8

Set latching behavior of minor fault and alarms.

Non-latching 0

Latching

1

Bit 0:

Alert

Bit1: Action1

Bit2: Action2

Bit3: Fire1

Bit4: Fire2

Bit5: Minor

336

½

Alert Delay

U8

Alert Alarm Delay in Seconds

337

½

Action1 Delay

U8

Action1 Alarm Delay in Seconds

338

½

Action2 Delay

U8

Action2 Alarm Delay in Seconds

339

½

Fire1 Delay

U8

Fire1 Alarm Delay in Seconds

340

½

Fire2 Delay

U8

Fire2 Alarm Delay in Seconds

341

½

Acclimate Enable

U8

Enable Acclimate Mode (use Acclimate Alarm Thresholds)

Disable

0

Enable

Not Zero

342-343

2

Day Time Start

U32

Epoch Local Time Stamp to mark the time in which to use

the day alarm thresholds.

344-345

2

Night Time Start

U32

Epoch Local Time Stamp to mark the time in which to use

the night alarm thresholds.

346-347

2

Alert Day Threshold

F32

Alert Alarm Day Obscuration Threshold

348-349

2

Alert Night Threshold

F32

Alert Alarm Night Obscuration Threshold

350-351

2

Alert Weekend Threshold

F32

Alert Alarm Weekend Obscuration Threshold

352-353

2

Action1 Day Threshold

F32

Action1 Alarm Day Obscuration Threshold

354-355

2

Action1 Night Threshold

F32

Action1 Alarm Night Obscuration Threshold

356-357

2

Action1 Weekend Threshold

F32

Action1 Alarm Weekend Obscuration Threshold

358-359

2

Action2 Day Threshold

F32

Action2 Alarm Day Obscuration Threshold

360-361

2

Action2 Night Threshold

F32

Action2 Alarm Night Obscuration Threshold

362-363

2

Action2 Weekend Threshold

F32

Action2 Alarm Weekend Obscuration Threshold

364-365

2

Fire1 Day Threshold

F32

Fire1 Alarm Day Obscuration Threshold

366-367

2

Fire1 Night Threshold

F32

Fire1 Alarm Night Obscuration Threshold

368-369

2

Fire1 Weekend Threshold

F32

Fire1 Alarm Weekend Obscuration Threshold

370-371

2

Fire2 Day Threshold

F32

Fire2 Alarm Day Obscuration Threshold