User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1

11

Rev A0

Sensor Status

The device’s Sensor Status Structure is READ ONLY with the exception of the Smoke Reference Value and mapped directly to a set

of holding registers. The structure in the Firmware is defined as follows:

Address

Size
(16-bit
words)

Parameter Name

Type

Description

40031-32

2

System Time

U32

Device Time in UNIX seconds epoch format, use Universal

Time Stamp instead.

33-34

2

Smoke Reference Value

F32

Smoke reference value used to increase noise floor of

detector.

US Standard Units Max: 0.10 (%/ft)

Metric Units Max: 0.328 (%/m)

35

1

Sensor Action Inputs

U16

All bits are self-clearing and will read ‘0’ after bit has been

read and processed

Bit 0:

1

Isolate – Toggles Isolate Mode

Bit1:

1

Disable – Toggles Disable Mode

Bit2:

1

Test – Place the device in Test Mode

Bit3:

1

Silence Sounder (if enabled / equipped)

Note: Sounder Silence is effective for a single alarm or fault

occurrence. If an alarm recurs, another alarm is initiated or

another fault occurs, the sounder will re-energize.

Bit4:

Reset Device

Bit5:

Reset Airflow Baselines

Current baseline cleared, and device will set a new

baseline. New baseline established within 15 minutes.

Bit6:

Clear Event Log Note: Allow this action up to 10

seconds to complete. Erases all Event Log entries

Bit7:

Clear Trend Log Note: Allow this action up to 5

seconds to complete. Erases all Trend Log entries

Bit8:

Clear Message Log Note: Allow this action up to 5

seconds to complete. Erases all Message Log entries

Bit9-15: Unused

36

½

Ch 1 Air Temperature

S8

Real-time sampled air temperature in Channel 1

37

½

Ch 1 Air Velocity Change

S8

Percentage change from baseline air velocity in Channel 1

38-39

2

Ch 1 Air Velocity Baseline

F32

Average velocity during baselining in Channel 1

40-41

2

Ch 1 Air Velocity Daily Min

F32

Daily minimum air velocity realized on Channel 1

42-43

2

Ch 1 Air Velocity Daily Max

F32

Daily maximum air velocity realized on Channel 1

44

½

Ch 2 Air Temperature

S8

Real-time sampled air temperature in Channel 2

(multichannel device only)

45

½

Ch 2 Air Velocity Change

S8

Percentage change from baseline air velocity in Channel 2

(multichannel device only)

46-47

2

Ch 2 Air Velocity Baseline

F32

Average velocity during baselining in Channel 2

(multichannel device only)

48-49

2

Ch 2 Air Velocity Daily Min

F32

Daily minimum air velocity realized on Channel 2

(multichannel device only)

50-51

2

Ch 2 Air Velocity Daily Max

F32

Daily maximum air velocity realized on Channel 2

(multichannel device only)