Sensor status (cont’d) – System Sensor FAAST Modbus User Manual

Page 12

Advertising
background image

User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1

12

Sensor Status (Cont’d)

Address

Size
(16-bit
words)

Parameter Name

Type

Description

52

½

Ch 3 Air Temperature

S8

Real-time sampled air temperature in Channel 3

(multichannel device only)

53

½

Ch 3 Air Velocity Change

S8

Percentage change from baseline air velocity in Channel 3

(multichannel device only)

54-55

2

Ch 3 Air Velocity Baseline

F32

Average velocity during baselining in Channel 3

(multichannel device only)

56-57

2

Ch 3 Air Velocity Daily Min

F32

Daily minimum air velocity realized on Channel 3

(multichannel device only)

58-59

2

Ch 3 Air Velocity Daily Max

F32

Daily maximum air velocity realized on Channel 3

(multichannel device only)

60

½

Ch 4 Air Temperature

S8

Real-time sampled air temperature in Channel 4

(multichannel device only)

61

½

Ch 4 Air Velocity Change

S8

Percentage change from baseline air velocity in Channel 4

(multichannel device only)

62-63

2

Ch 4 Air Velocity Baseline

F32

Average velocity during baselining in Channel 4

(multichannel device only)

64-65

2

Ch 4 Air Velocity Daily Min

F32

Daily minimum air velocity realized on Channel 4

(multichannel device only)

66-67

2

Ch 4 Air Velocity Daily Max

F32

Daily maximum air velocity realized on Channel 4

(multichannel device only)

68

½

Smoke Particulate Display

U8

Front panel particulate level (0-10)

69-70

2

Smoke Current Obs

F32

Current Obscuration Level the Smoke Sensor is Detecting

71-72

2

Smoke Daily Max Obs

F32

Maximum Obscuration Level the Smoke Sensor Detected

since 12am

73-74

2

Smoke Daily Min Obs

F32

Minimum Obscuration Level the Smoke Sensor Detected

since 12am

75-76

2

Alert Threshold

F32

Current Active Alert Threshold ( %/ft if US Standard or %/m

if metric)

77-78

2

Action1 Threshold

F32

Current Active Action1 Threshold ( %/ft if US Standard or

%/m if metric)

79-80

2

Action2 Threshold

F32

Current Active Action2 Threshold ( %/ft if US Standard or

%/m if metric)

81-82

2

Fire1 Threshold

F32

Current Active Fire1 Threshold ( %/ft if US Standard or %/m

if metric)

83-84

2

Fire2 Threshold

F32

Current Active Fire2 Threshold ( %/ft if US Standard or %/m

if metric)

85

1

Sensor Status

U16

Bit 0 – Admin Unlock

1 = Unlocked, 0 = Locked

Bit 1 –Baselining

1 = set (configured from sensor action inputs)

Table 4.

Sensor Status Modbus Holding Registers

Information - Registers 35 can be configured by using Function code 6(single write) or Function 16 (multiple write).

Warning!! Device threshold configuration variables should be set by the user to values scaled based on the Units configuration

setting. The detector will interpret the value differently for different Units settings. E.g. The device will interpret a 0.01 threshold

setting as 0.01 %/ft when Units setting is US Standard. The device will interpret a 0.01 threshold setting as 0.01 %/m when Units

setting is Metric.