1.2.2. ATRT-03A Technical Specifications

Table 2. ATRT-03A Technical Specifications

TYPE Portable, lightweight, automatic, battery-powered three-phase transformer

turns-ratio meter

PHYSICAL SPECIFICATIONS 19”W x 7”H x 15”D (48.2cm x 17.8 cm x 38.1 cm); Weight: 25 lbs (11.3 kg)

INPUT POWER

3 amps, 85 – 264 Vac or 110 – 370 Vdc or 12 Vdc

BATTERIES Two 12Vdc/2AH, rechargeable Sealed Lead Acid batteries (up to 3-hours

operation)

MEASUREMENT METHOD ANSI/IEEE C57.12.90

RATIO-MEASURING RANGE 0.8 – 15,000 (5-digit resolution)

TURNS-RATIO ACCURACY 0.8 – 1999: ±0.1%, 2,000 – 3,999: ±0.25%, 4,000 – 15,000: ±1% @ 8 Vac

0.8 – 1999: ±0.1%, 2,000 – 3,999: ±0.20%, 4,000 – 15,000: ±1% @ 40 Vac
0.8 – 1999: ±0.1%, 2,000 – 3,999: ±0.15%, 4,000 – 15,000: ±1% @ 100 Vac

ADJUSTMENT None required

TEST VOLTAGES 8 Vac @ 350 mA, 40 Vac @ 70 mA, 100 Vac @ 20 mA

EXCITATION CURRENT

READING RANGE

0 – 2 Amperes; Accuracy: ±1mA, ±2% of reading (±1 digit)

PHASE-ANGLE

MEASUREMENT

0 – 360 degrees; Accuracy: ±0.2 degrees ( ±1 digit)

DISPLAY Back-lit LCD screen (20 Characters by 4 Lines); Viewable in bright sunlight

and low-light levels

PRINTER

Built-in 4.5-inch wide thermal printer

COMPUTER INTERFACE

RS-232C (19,200 baud) port

PC SOFTWARE

Windows

®

XP/Vista-based Transformer Turns-Ratio Analyzer application is

included with purchase price

INTERNAL TEST RECORD

STORAGE

Stores 200 complete transformer test records. Each test record includes
nameplate voltage, winding turns-ratios, excitation current, and winding
phase angle.

INTERNAL TEST PLAN

STORAGE

Stores up to 128 transformer test plans

SAFETY

Designed to meet UL 61010A-1 and CAN/CSA C22.2 No. 1010.1-92
standards

ENVIRONMENT

Operating: -10˚ to 50˚ C (15˚ to +122˚ F); Storage: -30˚ C to 70˚ C (-22˚ to
+158˚ F)

HUMIDITY (MAX) 90% RH @ 40˚ C (104˚ F) non-condensing

ALTITUDE (MAX) 2000m (6562 ft) to fully safety specifications

CABLES

One 15-foot single-phase cable set, One 15-foot 3-phase cable set, One 25-
foot extension cable set, One cable-carrying duffel bag included

OPTIONS

Transportation case, transformer tap-changer remote control device

WARRANTY One year on parts and labor

NOTE

The above specifications are valid at nominal operating voltage and at a
temperature of 25

°C (77°F). Specifications may change without prior notice.