ATRT-03, ATRT-03A, AND ATRT-03B USER’S MANUAL

REV 7

15

3.0 OPERATING

PROCEDURES

The ATRT-03 should always be grounded with the provided ground cable before connecting H
and X cables. The transformer bushings should also be grounded before connecting test leads
to the transformer. This will prevent inducing any voltages into the ATRT-03. All transformer
bus connections must be removed, and the transformer must be isolated before performing
any tests. Typical transformer connection diagrams are illustrated in the sections below.

3.1 Connection

Diagrams

3.1.1. Typical Front Panel Connections

Figure 5. Typical Front Panel Cable Connections