Vanguard ATRT-03_03B User Manual

Page 77

Advertising
background image

ATRT-03, ATRT-03A, AND ATRT-03B USER’S MANUAL

REV 7

71

f. Start from the “START-UP” menu again to run a test using the loaded test plan from the

previous steps:

Press the

[1]

key (TEST XFMR).

g. The following screen will be displayed (test details will differ depending on the test type

defined in the test plan):

NOTE

The above screen will be displayed only if a test plan is loaded first.

Press the

[1]

key (CONTINUE).

h. The following screen will be displayed:

Press the

[1]

key (NO).

i. The following screen will be displayed:

Set the transformer to the tap position indicated on the LCD screen. Press the

[START]

key to run the test using the test plan.

j. The unit will start performing the test and the screen will be updated with the test

results as shown:

RATIO mA % DIFF
+10.022 0012 0.10P
+10.005 0011 0.06P
+10.023 0017 0.11P

TAP NUMBER 1
H VTG: 1,734
X VTG: 100
“START” to RUN TEST

STOP BETWEEN PHASES?
1.NO
2.YES

#1 Y-DELTA TAPS:20
TEST PLAN LOADED
1.CONTINUE
2.UNLOAD TEST PLAN

1.TEST XFMR 08/23/10
2.SETUP 08:25:15
3.CALCULATOR
4.DIAG 5.QUICK TST

Advertising