3.5

Using the Turns Ratio Calculator

The ATRT-03 features a turns ratio calculator that can be used to calculate the turns ratio for
various transformer types. The user only needs to provide the H and X name plate voltage
values. Follow the steps below to use the turns ratio calculator.

a. Start from the “START-UP” menu:

Press the

[3]

key (CALCULATOR).

b. The following screen will be displayed:

Select the transformer configuration by pressing the corresponding key on the keypad.
For this example, press the

[3]

key to select the Y-dT transformer type.

c. The following screen will be displayed:

Type the H name plate voltage value using the keypad and then press the

[ENTER]

key.

d. The following screen will be displayed:

Type the X name plate voltage value using the keypad and then press the

[ENTER]

key.

e. The following screen will be displayed showing the H and X name plate voltages along

with the calculated turns ratio:

Y to DELTA XFORMER
H: 1,734 V
X: 100 V
RATIO: 10.011

ENTER X WINDING

NAME-PLATE VOLTAGE:
V

ENTER H WINDING
NAME-PLATE VOLTAGE:
V

XFMR CONFIGURATION:

1.SNG PHS 2.dT-Y
3.Y-dT 4.dT-dT
5.Y-Y 6.SP TEST

1.TEST XFMR 08/16/10
2.SETUP 08:14:58
3.CALCULATOR
4.DIAG 5.QUICK TST

Advertising