<1. INTRODUCTION AND GENERAL DESCRIPTION>

1-12

IM 12A01A02-01E

5th Edition : Oct. 31, 2013-00

Electrical data are as follows;

Maximum Voltage (Ui) = 30V

Maximum Current (Ii) = 100mA

Maximum Power (Pi) = 0.75W

Internal Capacitance (Ci) = 13F

Internal Inductance (Li) = 0mH

Note 1: The output current must be limited by a resistor “R” such that Imaxout=Uz/R (linear source).

Note 2: Safety barrier certified by a notify body in EU as ATEX should be used.

Note 3: When using non isolation barrier, connect (*) to IS earthing system.

Note 4: Sensor module 2 is installed when required.

When measuring inductive conductivity, only one module can be installed.

Control Drawing (FM type)

Following contents refer “DOC. No. IKE039-A12”

Measuring module 1

Measuring module 2

(Refer to Note 7)

Sensor 1

Sensor 2

(Note 1)

Safety Barrier

Housing Assembly

Supply -

Supply +

Non Hazardous Location

Hazardous Location

-

+

Class I, Division 1, Groups A, B, C, and D

Class I, Zone 0 and 1, Group IIC

T4 for Ta = 55°C, T6 for Ta = 40°C

2 wire analyzer

Note: The measuring module on this drawing means

the sensor module on this General Specifications.

Electrical data are as follows;

Input Maximum Input Voltage (Ui) = 30V

Maximum Current (Ii) = 100mA

Maximum Power (Pi) = 0.75W

Internal Capacitance (Ci) = 13nF

Internal Inductance (Li) = 0mH

Sensor Input Circuit

Type of Measuring Module

pH, SC and DO

ISC

Maximum Voltage (Uo)

11.76 V

11.76 V

Maximum Current (Io)

116.5mA

60.6mA

Maximum Power (Po)

0.3424W

0.178W

External Capacitance (Ca, Co)

100nF

100nF

External Inductance (La, Lo)

1.7mH

8mH

Note 1: In any safety barrier used, the output current must be limited by a resistor “R” such that Imaxout=Uz/R.

Note 2: The safety barrier shall be FM Entity-Approved associated apparatus / barrier where :

Barrier Voc, Uo ≤ 30V;

Barrier Isc, Io ≤ 100 mA;

Barrier Po ≤ 0.75W;

Barrier Ca, Co ≥ 13 nF+Ccable;

Barrier La, Lo ≥ Lcable

Note 3: When using non isolation barrier connect (*1) to IS earthing system.

Note 4: pH and SC Sensor(s) are of a passive type to be regarded as ‘simple apparatus’ same as 06ATEX0218X,

06ATEX0219, IECEx KEM 06.0052X, FM3028779, 06ATEX0220X, 06ATEX0221, IECEx KEM 06.0053X or the one

individually certified with relevant parameters.

Note 5: ISC Sensor(s) are ISC40S of 00ATEX1067X or the one individually certified with relevant parameters.

Note 6: DO Sensor(s) are of a passive type to be regarded as ‘simple apparatus’ or the one individually certified with

relevant parameters.

Note 7: Measuring module 2 may not mounted. As for ISC module, only one can be mounted.

Note 8: Install per the National Electrical Code (NFPA 70)

Note 9: WARNING - Potential electrostatic charging hazard Electrostatic charge may cause an explosion hazard. Avoid any

actions that cause the generation of electrostatic charge, e.g., rubbing with a dry cloth.

Note 10: As an alternative to installing the FLXA21 in Division 2 using Class I, Division 2 wiring methods, the FLXA21 may

be installed in Division 2 using nonincendive field wiring in accordance with the National Electrical Code (NFPA

70) using the same parameters identified for intrinsically safe entity installations. The Associated Nonincendive

Apparatus shall have nonincendive field wiring connections which are FM Approved for use in the Class I, Division 2

location.