Cm sets the communication input data (/m1 option), Vc sets the batch comment (/bt1 option) – Yokogawa µR20000 User Manual

Page 61

Advertising
background image

4-18

IM 04P01B01-17E

Query

VD[p1]?

Example Assign the display in which different screens can

be assigned to the top and bottom sections to
screen 09. Set the top section to status display
and the bottom section to 1-channel digital
display. Switch the displayed channel every 3
seconds (parameters p5 to p7, p10, and p12
explained above are omitted).
VD09,Multiple display,STATUS,1CH
digital,AUTO3S

CM

Sets the communication input

data (/M1 option).

Syntax

CM p1,p2<terminator>
p1 Communication input data number (see

section 4.3)

p2 Communication input data

The selectable range is –9.9999E+29 to –
1.0000E–30, 0, 1.0000E–30 to 9.9999E+29.

(The + sign of “E+” can be omitted.)

Query

CM?

Example Set 1.0000E–10 to communication input data

number C01.
CMC01,1.0000E−10

FR

Sets the interval for acquiring

data to the FIFO buffer.

Syntax

FR p1<terminator>
p1 Pen model: 125ms, 250ms, 500ms, 1s, 2s,

2.5s, 5s, 10s

Dot model: 1s, 2s, 2.5s, 5s, 10s

Query

FR?

Example Set the acquiring interval to the FIFO buffer to 1 s.

FR1s

Description • Set the acquiring interval to an integer multiple

of the scan interval that is greater than the
scan interval.

• The scan interval on the pen model is 125 ms.
• The scan interval on the dot model varies

depends on the integration time of the A/D
converter as follows:
When the integration time is 16.7 ms or 20 ms;
6 channels: 1 s
12, 18, or 24 channels: 2.5 s
When the integration time is 100 ms;
6 channels: 2.5 s
12 channels: 5 s
18 and 24 channels: 10 s

VH

Sets the batch number and lot

number (/BT1 option).

When setting the batch number

Syntax

VH p1,p2<terminator>
p1 BATCH
p2 Batch number (up to 26 characters)

Query

VH[p1]?

Example Set character string Product as a batch number.

VHBATCH,Product

Description Valid with the header printout (/BT1 option) when

set to use Start printout/End printout (see the UE
command).

When setting lot number for the 4 digits

Syntax

VH p1,p2<terminator>
p1 LOT
p2 0000-9999

Query

VH[p1]?

Example Set 0001 as the lot number.

VHLOT,0001

Description Valid with the header printout (/BT1 option)

when lot number is set to 4 digits (see the UE
command).

When setting lot number for the 6 digits

Syntax

VH p1,p2<terminator>
p1 LOT
p2 000000-999999

Query

VH[p1]?

Example Set 000001 as the lot number.

VHLOT,000001

Description Valid with the header printout (/BT1 option)

when lot number is set to 6 digits (see the UE
command).

VC

Sets the batch comment

(/BT1 option).

Syntax

VC p1,p2,p3<terminator>
p1 Mode selection

START Start printout
END

End printout

START2 Start printout 2
END2

End printout 2

p2 line number (up to 5)
p3 Batch comment

(µR10000: up to 32 chars., µR20000: up to
64 chars.)

Query

VC[p1[,p2]]?

Example Set the string Batch start to the first line of the

Start printout batch comment.
VCSTART,1,Batch start

Description • Valid with the header printout (/BT1 option)

when set to use Start printout/End printout (see
the UE command).

• Start printout 2 and End printout 2 valid when

set to use Start printout 2 and End printout 2
(see the UE command).

4.4 Setting Commands

Advertising
This manual is related to the following products: