5.5.2.4. Vectors
This screen (Fig. 148) displays, with graphic and numeric indications, the phase delays
expressed in degrees [°] between:

 Voltage V1 and V2, V2 and V3, V3 and V1.

 Voltage V1 and current I1.

 Voltage V2 and current I2.

 Voltage V3 and current I3.

The latter allow finding out the inductive or capacitive nature of the electrical installation. In
detail:
 Positive angle: Inductive load.

 Negative angle: Capacitive load.

The N-PE voltage (blue) and Neutral current (pale blue) vectors are also represented.

Fig. 148: Total vector diagram in three-phase 4-wire system

The following keys are active on this page:

 The F1 key (or the PAG item on the display) advances to the following page of saved

values relative to the voltage vector diagram.

 The ESC key (or the smart icon on the display) to exit the function and go back to the

“Recording analysis” page (Fig. 124).