Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013

Technical Data


IMPORTANT

The following information is for general guidance; refer to the certified drawings provided
for installation.

CAUTION

ALL work MUST be carried out by technically trained competent personnel.

The equipment contains live electrical and moving parts, ISOLATE prior to maintenance
or repair work.

A fused and isolated electrical supply of the appropriate rating should be installed.
As standard the equipment is designed for 230V

10%, 1 Phase, 50Hz to all relevant IEE

regulations, British standards and IEC requirements.


Design Parameters


The OnRak is designed for operation at air on dry bulb temperatures and water approach temperatures as standard:





























* Minimum water temperature is always 2°C above the dew point temperature of the air

Approach Water Temperature*

Air On to Coil
(Server Discharge)

60°C

16°C

10°C

46°C

18°C

Normal

working

area

Application

limits

20°C

0.0105 /
(7%RH)

0.0065 /
(57%RH)

moisture

content

kg/kg (dry

air)