Maintenance, It cooling logicool ™ onrak – Airedale OnRak 3kW 35kW User Manual

Page 53

Advertising
background image

IT Cooling

LogiCool

™ OnRak

IT Cooling

53

Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013

Maintenance

Changing EC Fans

The fans are designed as plug and play “hot swap” enabling the fans to be changed
without the need to disconnect the power from the entire unit.
Removing the 4 security fixings enable the fan to be removed

The unit has automatic disconnect sockets to the fan motors. The remaining fans will
increase speed to compensate for the fan being serviced (only in N+1 configuration)

CAUTION

The unit will remain live up to the fan disconnect socket.

Ensure that the fan stops rotating before placing hand near blades.

2 or 3 Way Chilled
Water Regulating
Valve

The 2 or 3 way chilled water regulating valve actuator must be inspected to ensure a
secure fixing to the valve body. The actuator is located onto the valve body by four pegs
that are secured by a torque screw through the adjustment handle.

Coil Guard Cleaning

The coil guard must be cleaned periodically. Carefully removing any debris.
Be careful not to damage the temperature sensors.

CAUTION

When cleaning the coil guard, extreme care must be taken to ensure that the coil
does not get damaged.