Operational maintenance checks, Owners responsibility, Maintenance schedule – Airedale OnRak 3kW 35kW User Manual

Page 54: Logicool ™ onrak active cabinet exhaust it cooling

Advertising
background image




LogiCool

™ OnRak



Active Cabinet Exhaust

IT Cooling

54

IT Cooling

Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013

Operational Maintenance checks


Owners Responsibility


To ensure that the unit can be maintained correctly the following requirements are required.

Maintain a safe working environment around the unit, free from obstructions and debris.

The unit shall follow the following maintenance regime as a minimum.

The equipment contains live electrical and moving parts, ISOLATE prior to maintenance or repair work.

Ensure Lock off procedures is carried out accordingly.

Maintenance Schedule

Item

Task

Frequency

Unit Inspection

6 Mths

12 Mths

60 Mths

General
Inspections

Check for visible mechanical damage to unit.

Check for cleanliness

Visually inspect the unit for general wear and tear, treat
metalwork.

Rust should be inhibited, primed and touched up with matching paint.

Check for excess vibration from other rotating equipment.

Coil Guard
Cleaning

Ensure that the coil guard is free from debris.

Electrical
Inspection

Check main power supply voltages

Check electrical terminals are tight.

Check that the control panel and fan assembly cables are
securely fastened together.

Check amperages are as per design.

Controls alarm log

Check alarm log for any spurious events.

Dual Power Supply

Check operation of dual power supply.

Static Transfer
Switch

Check operation of static transfer switch. Referrer to
manufacturer information.

Uninterrupted
Power Supply

Check operation of UPS. Ensure battery within UPS is
holding charge.

Service tools / Test Equipment

Voltmeter

Screwdrivers/ Allen keys

Safety Equipment

Safety Glasses/ Goggles

Advertising