Rack pressure management, Logicool ™ onrak active cabinet exhaust it cooling – Airedale OnRak 3kW 35kW User Manual

Page 50

Advertising
background image




LogiCool

™ OnRak



Active Cabinet Exhaust

IT Cooling

50

IT Cooling

Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013

Rack Pressure Management


The fans will operate to maintain the “air off” temperature as long as the pressure remains within the normal operating
range. However, if the pressure within the server space changes beyond the high or low differential set-points, the fans
prioritise pressure control to bring the server pressure back within limits, at which point normal temperature control
resumes.
























The diagram shows the normal operating area between the dotted lines (B) of the low and high set-point differentials.
The red zones (A and C) indicate areas where the fans prioritise pressure control to bring it back within limits.

100%

Fan
Speed

-100%

Fan Minimum

Speed

Low Set-point

(-40Pa)

Low Set-point

Differential

(-30Pa)

High Set-point

Differential

(0Pa)

High Set-point

(10Pa)

Fan
Speed

Fan Maximum

Speed

Temperature control is

affected as the fan speed is

increased to control pressure

0%

0%

Normal operating

range which is not

influenced by

pressure control

Temperature control is

affected as the fan speed is
reduced to control pressure

A

B

C