Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013

Chilled Water Valve
(3 Way)

The chilled water valve has an indication of flow on the stem. The actuator is securely
attached to the top of the valve so that when there is a demand for cooling the valve
opens allowing water to flow through the coil. No demand, the water goes through the
bypass (0 VDC no demand, 10 VDC 100% demand).















(A) Flow to coil
(B) Bypass leg
(C) Common






Valve in full flow to coil (C to A)


Valve in flow to bypass (C to B)

Valve Actuator Orientation

CAUTION

The chilled water valve electrical connection must be a maximum of 3m away from
the customer terminal box. This is to ensure EMC Compatibility.