Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013

Under Floor Dual Power
Supply

The under floor Dual Power supply is located under the floor void. The supply is to be
mounted securely. Provision is made for fixing to the floor or associated supports.

Attach relevant earth bonding to the power supply.

Attach the incoming fused power supplies. (The Primary supply for this supply
is always “A”.)

Fit power supply retaining clips.

Attach the outgoing power supply to the customer terminal box.

The dual power supplies use C14 / C13 socket combinations for ease of use.

CAUTION

The OnRak must have relevant over current protection

(MCB’s) upstream of the

unit.


Out Going

Supply A

Supply B