LogiCool

™ OnRak



Active Cabinet Exhaust

IT Cooling

32

IT Cooling

Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013

Chilled Water Valve
(2 Way)

The chilled water valve has an indication of flow on the stem.

The actuator is securely attached to the top of the valve so that when there is a demand
for cooling the valve opens allowing water to flow through the coil. No demand, the water
is shut off allowing no water to enter the coil (0 VDC no demand, 10 VDC 100% demand).



(A) Flow to coil
(C) Common

Valve in full flow to coil (C to A)


Valve in shut off mode


Valve connection sizes 1”BSP.

A

B

C

D

E

F

G*

100

19

33

141

87

9

43

* for 3 way valves only

CAUTION

The chilled water valve electrical connection must be a maximum of 3m away from
the customer terminal box. This is to ensure EMC Compatibility.

A

C