Sound Measurement Method


Measurement of Sound
Data

All sound data quoted has been measured in the third-octave band limited values,
using a real time analyser calibrated sound intensity meter in accordance with BS
EN ISO9614 Part 1: 1995.

All sound power levels quoted are calculated from measured sound intensity
according to BS EN ISO9614 Part 1: 1995.


Semi Hemispherical

Sound pressure levels are calculated from sound power using the semi-
hemispherical method where the noise source is in junction with 1 boundary i.e. the
floor.


Free Field

For comparison, the semi hemispherical figures can typically be reduced by 3dB to
provide free field conditions.


Specialist acoustic advice is recommended for noise critical applications.


Noise Data

LOR 6042U-C028-0

Frequency (Hz)

Overall

63

125

250

500

1000

2000

4000

8000

Sound Pressure @ 1m dB(A)

62

35

43

48

58

57

55

51

39


LOR 6042U-C033-0

Frequency (Hz)

Overall

63

125

250

500

1000

2000

4000

8000

Sound Pressure @ 1m dB(A)

67

42

46

53

61

62

60

56

47


LOR 8042U-C032-0

Frequency (Hz)

Overall

63

125

250

500

1000

2000

4000

8000

Sound Pressure @ 1m dB(A)

62

35

43

48

58

57

55

51

39


LOR 8042U-C038-0

Frequency (Hz)

Overall

63

125

250

500

1000

2000

4000

8000

Sound Pressure @ 1m dB(A)

67

42

46

53

61

62

60

56

47