Blue-White CHEM-PRO C3 ProSeries Diaphragm Pump User Manual
Page 10
Page 11
Chem-Pro
Chem-Pro
®
®
Press and release
Press DOWN arrow to decrease pump speed
(output) in Manual Operation.
To decrease value while in programming mode.
6.0
How to Operate Chem-Pro® - Control Pad
Press and release
To prime pump (60 seconds) --See page 27
Press and hold
To enter programming mode.
Ÿ
Remote Start/Stop setup
Ÿ
FVS (flow verification sensor) setup
Press and release
To save setting while in programming mode.
To move to next selection while in programming
mode.
Press and release
Press UP arrow to increase pump speed (output)
in Manual Operation.
To increase value while in programming mode.
Press and release
To Stop pump at any time.
Press and release
To Start pump.
To begin listening (reacting) to external signal,
such as Remote Start/Stop.
Page 10
START
STOP
START
STOP
PRIME
MODE
Press and release
To select Run Mode
Mode 1: Manual
Mode 2: 4-20mA input
Mode 3: Frequency input
Mode 4: Pulse / Batch
Press and Hold
To configure selected Mode
Mode 0: Setup
Mode 1: Manual
Mode 2: 4-20mA input
Mode 3: Frequency input
Mode 4: Pulse / Batch
Mode 0 - Setup
Press and Hold to configure:
Ÿ
Remote Start / Stop
Ÿ
DFD (Diaphragm Failure Detection) sensitivity
Ÿ
FVS (Flow Verification Sensor) time delay - requires sensor
Ÿ
4-20 mA output, available on certain models
Mode 0
Mode 1 - Manual
Run pump locally by selecting pump speed (1 - 100%).
Ÿ
Control speed by using up or down arrows after start button is
pressed.
Ÿ
Control speed by entering Mode 1 setup and selecting desired
pump speed (1 - 100%)
Mode 2 - 4-20 mA Input Signal
Run pump remotely via external 4-20 mA signal.
Ÿ
Press and Hold “MODE” button with Mode 2 selected to
configure settings.
Ÿ
Select Mode 2 and press START button to allow pump to be
controlled by external 4-20mA signal.
Mode 3 - Frequency (Hz) Input Signal
Run pump remotely via external high frequency (Hz) signal.
Ÿ
Press and Hold “MODE” button with Mode 3 selected to
configure settings.
Ÿ
Select Mode 3 and press START button to allow pump to be
controlled by external frequency (Hz) signal.
Mode 4 - Pulse Batch Input Signal
(low speed pulse)
Run pump remotely via external low speed pulse signal.
Ÿ
Press and Hold “MODE” button with Mode 4 selected to
configure settings.
Ÿ
Select Mode 4 and press START button to allow pump to be
controlled by external low speed pulse signal.
SEt
0
Mode 1
OFF
1
Mode 2
OFF
2
Mode 3
OFF
3
Mode 4
OFF
4
SPEED
mA
Hz
Hz
ON
6.1
Mode Descriptions
Time-out - Chem-Pro® pumps have a time-out setting of approximately 20 seconds while in configuration menu. If built-in timer
exceeds 20 seconds without a button being pressed, then pump will exit configuration menu. Changes will automatically be saved if
programming mode is allowed to Time-Out.