0 output versus pressure, Chem-pro, Chem-pro 17.0 dfd (diaphragm failure detection) – Blue-White CHEM-PRO C3 ProSeries Diaphragm Pump User Manual
Page 32: Typical installation, Page 33, Page 32
Page 33
®
®
18.0 Output Versus Pressure
0
5
10
Feed Rate US GPH
15
20
0
25
5
10
15
20
Feed Rate US GPH
25
Small Diaphragm, Max 175 PSIg / 12 bar
Model: C2x2x1
166 RPM
Small Diaphragm
.060” Offset
Large Diaphragm, Max 175 PSIg / 12 bar
Model: C2x2x2
166 RPM
Large Diaphragm
.060” Offset
0
25 (1.7)
50 (3.4)
75 (5.2)
100 (6.8)
125 (8.6)
150 (10.3)
PSIg (Bar)
0
25 (1.7)
50 (3.4)
75 (5.2)
100 (6.8)
125 (8.6)
150 (10.3)
PSIg (Bar)
Feed Rate LPH
95
18.9
37.9
56.8
75.7
Feed Rate LPH
95
18.9
37.9
56.8
75.7
0
25
5
10
15
20
Feed Rate US GPH
Small Diaphragm, Max 175 PSIg / 12 bar
Model: C2x2x3
166 RPM
Small Diaphragm
.040” Offset
0
25 (1.7)
50 (3.4)
75 (5.2)
100 (6.8)
125 (8.6)
150 (10.3)
PSIg (Bar)
Feed Rate LPH
95
18.9
37.9
56.8
75.7
175 (12.0)
175 (12.1)
175 (12.1)
18.1 C2 Output V. Pressure
17.2 C3 Output V. Pressure
175 (12.1)
0
25 (1.7)
50 (3.4)
75 (5.2)
100 (6.8)
125 (8.6)
150 (10.3)
0
50
10
20
30
40
Feed Rate US GPH
0
5
10
Feed Rate US GPH
15
20
25
Maximum 100 PSIg / 5.5 bar
Model: C3x2x2
130 RPM
.100 Stroke Length
PSIg (Bar)
Maximum 150 PSIg / 10.3 bar
Model: C3x2x1
130 RPM
.060 Stroke Length
175 (12.1)
0
25 (1.7)
50 (3.4)
75 (5.2)
100 (6.8)
125 (8.6)
150 (10.3)
PSIg (Bar)
Feed Rate LPH
95
18.9
37.9
56.8
75.7
Feed Rate LPH
95
18.9
37.9
56.8
75.7
Foot Valve
CHEM-PRO
TM
tm
CHEM-PRO
C3V | Diaphragm Metering Pump
Made in the USA
MODE
PRIME
Program
Minimum
Maximum
Blue-White Ind.
IP66
NEMA 4X
Suction Tubing
Injection /
Check Valve
Chemical Tank
Priming /
Degassing Tubing
Discharge Tubing
Page 32
Chem-Pro
Chem-Pro
17.0 DFD (Diaphragm Failure Detection)
Chem-Pro® is equipped with a Diaphragm Failure Detection System which is designed to stop pump and provide
an output alarm in event diaphragm should rupture and chemical enters pump head. Pump will detect a chemical
with a conductivity reading greater than 500 microsiemens. Chemicals with a conductivity of less than 500
microsiemens will not be detected.
This system is capable of detecting
presence of a large number of
chemicals including Sodium
Hypochlorite (Chlorine),
Hydrochloric (muriatic) Acid, Sodium
Hydroxide, and many others. System
will not be triggered by water (rain,
condensation, etc.) or lubricants.
If system has detected chemical,
pump diaphragm must be replaced
and pump head must be thoroughly
cleaned. Failure to clean pump head
will void warranty.
If DFD alarm occurs, pump will stop,
close an alarm output, and screen
will flash DFD with an alarm icon.
DFD
DFD Sensors
Diaphragm
Diaphragm
Outlet
(discharge)
Built -In DFD
Diaphragm Failure
Detection
Inlet
(suction)
Pump
Head
Typical Installation