Blue-White CHEM-PRO C3 ProSeries Diaphragm Pump User Manual

Page 17

Advertising
background image

Page 16

Page 17

Chem-Pro

Chem-Pro

®

®

Available on certain models.

Sends a configurable 4-20 mA signal, based on pump rotor speed, to an external device. This feature can be
used to control other pumps (in sync / proportionally), data logging systems, and other external devices for plant
automation.

Default setting: Minimum Speed = 4 mA signal output

Maximum Speed = 20 mA signal output

Set to NO = disabled
Set to Yes = enabled

Step 1

Ensure pump is stopped and LCD reads “OFF.”

Note: Mode cannot be changed while pump is in running.

Press and release STOP button if pump is running.
Press and release MODE button multiple times until Mode 0
is selected.

Step 2

With Mode 0 selected, press and hold MODE button until
‘Remote’ icon begins flashing.
This indicates that you’ve entered Setup menu.

Step 3

Press and release MODE button to scroll through menu until
you see 4-20 mA icon.
To select Yes, press and release DOWN arrow.
To select No, press and release UP arrow.
To begin configuring values, select Yes.
Then press and release MODE button.

Step 4

Minimum pump speed will be displayed.
To increase value, press and release UP arrow.
To decrease value, press and release DOWN arrow.
To save value, press and release MODE button.

Mode 0

SEt

0

yes

0

Mode 0

no

0

REMOTE

Remote

Icon

Mode 0

Step 8

You can now modify other settings in Mode 0 or you can exit
Setup by; press and hold MODE button for a few seconds
until you return to Run screen.

Mode 0

set

0

M

A

OUT

4-20 mA Icon

Mode 0

6

4

8 10 12 14 16 18 20

0

25

50

75

100

Pump Motor Speed (%)

Milliamp Output (mA) Signal

Default Setting

0.1

0

M

A

OUT

4-20 mA Icon

SPEED

MIN

Step 5

Output signal at minimum speed will now be displayed.
To increase value, press and release UP arrow.
To decrease value, press and release DOWN arrow.
To save value, press and release MODE button.

4

M

A

OUT

4-20 mA Icon

MIN

Step 6

Maximum pump speed will be displayed.
To increase value, press and release UP arrow.
To decrease value, press and release DOWN arrow.
To save value, press and release MODE button.

Mode 0

100.0

0

M

A

OUT

4-20 mA Icon

SPEED

Step 7

Output signal at maximum speed will now be displayed.
To increase value, press and release UP arrow.
To decrease value, press and release DOWN arrow.
To save value, press and release MODE button.

20.0

M

A

OUT

4-20 mA Icon

Mode 0

0

Example 1

6

4

8 10 12 14 16 18 20

0

25

50

75

100

Pump Motor Speed (%)

Milliamp Output (mA)

Signal

0% Pump Output = 4 mA
100 % Pump Output = 20 mA

Example 2

6

4

8 10 12 14 16 18 20

0

25

50

75

100

Pump Motor Speed (%)

Milliamp Output (mA)

Signal

0% Pump Output = 4 mA
50% Pump Output = 16 mA

7.3

Mode 0 - Set 4-20mA Output

7.3

Mode 0 - Set 4-20mA Output - Continued

Time-out - Chem-Pro® pumps have a time-out setting of approximately 20 seconds while in configuration menu. If built-in timer
exceeds 20 seconds without a button being pressed, then pump will exit configuration menu. Changes will automatically be saved if
programming mode is allowed to Time-Out.

Only available on certain models