Blue-White CHEM-PRO C3 ProSeries Diaphragm Pump User Manual

Page 21

Advertising
background image

Page 20

Page 21

Used to remotely control pump with an incoming 4-20 mA signal.

Default setting: 4 mA signal = 0.1% motor speed

20 mA signal = 100.0% motor speed

Step 1

Ensure pump is stopped and LCD reads “OFF.”

Note: Mode cannot be changed while pump is in running.

Press and release STOP button if pump is running.
Press and release MODE button multiple times until Mode 2
is selected.

Step 2

With Mode 2 selected, press and hold MODE button until
‘Speed’ icon begins flashing.
This indicates that you’ve entered Setup menu.

Step 3

Minimum pump speed will be displayed.
To increase value, press and release UP arrow.
To decrease value, press and release DOWN arrow.
To save value, press and release MODE button.

Step 5

Maximum pump speed will be displayed.
To increase value, press and release UP arrow.
To decrease value, press and release DOWN arrow.
To save value, press and release MODE button.

Mode 2

Step 7

To exit Setup, press and hold MODE button for a few
seconds until you return to Run screen.

6

4

8 10 12 14 16 18 20

0

25

50

75

100

Pump Motor Speed (%)

Milliamp Output (mA) Signal

Default Setting

2

SPEED

Step 6

mA value linked to minimum pump speed will now be
displayed.
To increase value, press and release UP arrow.
To decrease value, press and release DOWN arrow.
To save value, press and release MODE button.

20

M

A

Mode 2

0.1

Mode 2

OFF

mA

MIN

2

SPEED

2

100.0

Step 4

mA value linked to minimum pump speed will be
displayed.
To increase value, press and release UP arrow.
To decrease value, press and release DOWN arrow.
To save value, press and release MODE button.

2

M

A

Mode 2

4.0

MIN

Mode 2

0.1

MIN

2

SPEED

2

Mode 2

Mode 2

OFF

mA

2

Example 1

6

4

8 10 12 14 16 18 20

0

25

50

75

100

Pump

Motor Speed (%)

Milliamp input (mA)

from external source

4 mA = 0% Pump Output

20 mA = 100% Pump Output

Example 2

6

4

8 10 12 14 16 18 20

0

25

50

75

100

4 mA = 100% Pump Output

20 mA = 0% Pump Output

Example 3

6

4

8 10 12 14 16 18 20

0

25

50

75

100

4 mA = 20% Pump Output

16 mA = 43.8% Pump Output

0%

Output

Pump

Motor Speed (%)

Pump

Motor Speed (%)

100%

Output

100%

Output

0%

Output

43.8%

Output

20%

Output

Milliamp input (mA)

from external source

Milliamp input (mA)

from external source

Runtime Screen Shot 1

Mode 2

9.1

Mode 2 - 4-20mA Input Screen Shots

Runtime Screen Shot 2

Mode 2

9.6

mA

2

9.0

Mode 2 - 4-20mA Input Operation

9.0

Mode 2 - 4-20mA Input Operation - Continued

Display motor speed percentage.
Pump Running in 4-20mA Input Operation

Display current 4-20mA input signal
Press and release MODE button to view mA input value
in real-time.

35.0

SPEED

2

Runtime Screen Shot 3

Mode 2

9.6

mA

2

Press and release MODE button again to view mA output
value in real-time

(available on select models only)

.

Press and release MODE button again to view motor
speed percentage
, as in Screen Shot 1.

OUT

®

®

Chem-Pro

Chem-Pro

MODE

MODE

Time-out - Chem-Pro® pumps have a time-out setting of approximately 20 seconds while in configuration menu. If built-in timer
exceeds 20 seconds without a button being pressed, then pump will exit configuration menu. Changes will automatically be saved if
programming mode is allowed to Time-Out.

Only available on certain models