D. fresh air supply – American Dryer Corp. Gas- DSI/Steam ML-82 II User Manual

Page 17

Advertising
background image

13

IMPORTANT: When fire sprinkler systems are located above the dryers, a minimum of 18-inches

(45.72 cm) above the dryer console (module) is required. Dryers may be positioned
sidewall to sidewall. However, a 1/16-inch (1.5875 mm) minimum allowance is
required between dryers (or wall) for ease of installation and maintenance.
Allowances must be made for the opening and closing of the control door and the lint
door.

D. FRESH AIR SUPPLY

When the dryer is operating, it draws in room air, heats it, passes this air through the basket (tumbler), and
exhausts it out of the building. Therefore, the room air must be continually replenished from the outdoors. If the
make-up air is inadequate, drying time and drying efficiency will be adversely affected. Ignition problems and sail
switch “fluttering” problems may result, as well as premature motor failure from overheating.

Air supply (make-up air) must be given careful consideration to assure proper performance of each dryer. An
unrestricted source of air is necessary for each dryer. An airflow of 1,700 cfm (cubic feet per minute) - 48.14
cmm (cubic meters per minute) - must be supplied to each dryer. As a general rule, an unrestricted air entrance
from the outdoors (atmosphere) of a minimum of 2-1/2 square feet (0.23 square meters) is required for each
dryer.

To compensate for the use of registers or louvers used over the openings, this make-up air must be increased by
approximately thirty-three percent (33%). Make-up air openings should not be located in an area directly near
where exhaust vents exit the building.

Advertising