American Dryer Corp. Gas- DSI/Steam ML-82 II User Manual

Page 21

Advertising
background image

17

a. Outside Ductwork Protection

1) To protect the outside end of the horizontal ductwork from the weather, a 90° elbow bent downward

should be installed where the exhaust exits the building. If the ductwork travels vertically up
through the roof, it should be protected from the weather by using a 180º turn to point the opening
downward. In either case, allow at least twice the diameter of the duct between the duct opening
and the nearest obstruction.

IMPORTANT: DO NOT use screens, louvers, or caps on the outside opening of the exhaust

ductwork.

3. Multiple Dryer (Common) Venting

If it is not feasible to provide separate exhaust ducts for each dryer, ducts from individual dryers may be
channeled into a “common main duct.” The individual ducts should enter the bottom or side of the main duct
at an angle not more than 45º in the direction of airflow and should be spaced at least 38-1/4” (97.15 cm)
apart. The main duct should be tapered, with the diameter increasing before each individual duct (14-inch
[35.56 cm] minimum for gas models and 16-inch [40.64 cm] minimum for steam models) is added.

IMPORTANT: No more than four (4) dryers should be connected to one (1) main common duct.

The main duct may be any shape so long as the minimum cross-sectional area is provided. The illustration
on page 18 shows the minimum cross section area for multiple dryer round or square venting. These
figures must be increased 10 square inches (64.52 squares centimeters) when rectangular main ducting is
used, and the ratio of duct width to depth should not be greater than 3-1/2 to 1. These figures must be
increased in proportion if the main duct run to the last dryer to where it exhausts to the outdoors is unusually
long (over 15 feet [4.57 meters]) or has numerous (more than two [2]) elbows in it. In calculating ductwork
size, the cross section area of a square or rectangular duct must be increased twenty percent (20%) for
each additional 15 feet (4.57 meters). The diameter of a round exhaust must be increased ten percent
(10%) for each additional 15 feet (4.57 meters). Each 90º elbow is equivalent to an additional 30 feet (9.14
meters) and each 45º elbow is equivalent to an additional 15 feet (4.57 meters).

IMPORTANT: For extended ductwork runs, the cross section area of the ductwork can only be

increased to an extent. Maximum proportional ductwork runs, cannot exceed 15 feet
(4.57 meters) more than the original limitations of 15 feet (4.57 meters) with two (2)
elbows. When the ductwork approaches the maximum limits as noted in this manual,
a professional heating, venting, and air conditioning (HVAC) firm should be consulted
for proper venting information.

IMPORTANT: Exhaust back pressure measured by a manometer at each dryer exhaust duct area

must not exceed 0.3 inches (0.74 mb) of water column (W.C.).

The ductwork should be smooth inside with projections from sheet metal screws or other obstructions
which will collect lint. When adding ducts, the duct to be added should overlap the duct to which it is to be
connected. ALL ductwork joints must be taped to prevent moisture and lint from escaping into the building.
Inspection doors should be installed at strategic points in the exhaust ductwork for periodic inspection and
cleaning of lint from the ductwork.

Advertising