American Dryer Corp. Gas- DSI/Steam ML-82 II User Manual

Page 19

Advertising
background image

15

IMPORTANT: Exhaust back pressure measured by a manometer in the exhaust duct must not

exceed 0.3 inches (0.74 mb) of water column (W.C.).

NOTE: When the exhaust ductwork passes through a wall, ceiling, or roof made of combustible

materials, the opening must be 2-inches (5.08 cm) larger than the duct (ALL the way around).
The duct must be centered within this opening.

a. Outside Ductwork Protection

1) To protect the outside end of horizontal ductwork from the weather, a 90º elbow bent downward

should be installed where the exhaust exits the building. If the ductwork travels vertically up
through the roof, it should be protected from the weather by using a 180º turn to point the opening
downward. In either case, allow at least twice the diameter of the duct opening and the nearest
obstruction.

IMPORTANT: DO NOT use screens, louvers, or caps on the outside opening of the exhaust

ductwork.

2. Single Dryer Venting

Where possible, it is suggested to provide a separate exhaust duct for each dryer. The exhaust duct should
be
laid out in such a way that the ductwork travels as directly as possible to the outdoors with as few turns
as possible. It is suggested that the use of 90° turns in the ducting be avoided; use 30° and/or 45° angles
instead. The shape of the exhaust ductwork is not critical so long as the minimum cross section area is
provided.

IMPORTANT: For a dryer that is vented horizontally, the minimum duct size for a gas dryer is

14-inches (35.56 cm) for a round duct or 12-1/2” (31.75 cm) for a square duct.
THE DUCT SIZE MUST NOT BE REDUCED ANYWHERE
DOWNSTREAM OF THE DRYER
.

Advertising