9.0 Wind Turbine Operation

NOTICE: Use of the material contained in this document is subject to the warning on page Iv and the disclaimer

on page v of this document.


DOC012R02 AOC 15/50 User Manual Nov 2001

76

9.1.7.1 PLC Inputs


The following tables list and describe the input signals to the PLC controlling the AOC 15/50.

Function

Description


Anemometer #1


0-5 VDC analog signal corresponds to 0-45 m/s (0-100 mph).


Anemometer #2


0-5 VDC analog signal corresponds to 0-45 m/s (0-100 mph).


Generator speed proximity
switches #1 and #2


Pulse input to F/V converter. 1-5 VDC signal corresponds to 0
to 2,000 rpm.


Watts Transducer Control


0-5 VDC analog signal corresponds to 0-8 kW.

Table 9.1-6 PLC low level analog inputs

Function

Description


Generator thermal switch


3 series connected switches within the generator.


Grid Voltage monitor


Relay contact indicating loss of phase, phase reversal and under
or over voltage.


Grid Frequency monitor
(optional)


Relay contact indicating over or under frequency.


Master control relay


Used to determine whether or not the turbine has been reset.


Turbine OFF/TEST/ON


Maintained switch parks or starts the turbine. In test position it
allows special test functions to become active.


Rotor jog switch


Maintained switch releases the brakes and connects the turbine
to the grid. Available in test mode.


Parking brake release switch


Maintained switch releases the parking brake. Available in test
mode.


Dynamic brake test switch


Maintained switch used in combination with the rotor jog
switch to delay operation of the tip and parking brakes to verify
the effectiveness of the dynamic brake. Available in test mode.


Remote start (optional)


Allows a turbine to be started by another turbine's controller; its
own anemometers (if equipped) are ignored.


Remote line start (optional)


Causes an across the line start if remote start is true.