Temperature requirements, Power requirements, 30 power requirements – HP Secure Key Manager User Manual

Page 30

Advertising
background image

When vertical space in the rack is not filled by an SKM or rack component, the gaps between the
components cause changes in airflow through the rack and across the servers. Cover all gaps with
blanking panels to maintain proper airflow. Using a rack without blanking panels results in improper
cooling that can lead to thermal damage.

The Compaq 10000 Series racks provide proper SKM cooling from flow-through perforations in the
front and rear doors that provide 64 percent open area for ventilation.

CAUTION:

If a third-party rack is used, observe the following additional requirements to ensure adequate airflow
and to prevent damage to the equipment:

Front and rear doors—If the 42U rack includes closing front and rear doors, you must allow 5,350
sq cm (830 sq in) of holes evenly distributed from top to bottom to permit adequate airflow
(equivalent to the required 64 percent open area for ventilation).

Side—The clearance between the installed rack component and the side panels of the rack must
be a minimum of 7 cm (2.75 in).

Temperature requirements

To ensure continued safe and reliable equipment operation, install or position the system in a
well-ventilated, climate-controlled environment.

The maximum recommended ambient operating temperature (TMRA) for the SKM system is 35° C
(95° F). The temperature in the room where the rack is located must not exceed 35° C (95° F).

CAUTION:

To reduce the risk of damage to the equipment when installing third-party options:

Do not permit optional equipment to impede airflow around the SKM or to increase the internal
rack temperature beyond the maximum allowable limits.

Do not exceed the TMRA.

Power requirements

Installation of an SKM must comply with local and regional electrical regulations governing the
installation of information technology equipment by licensed electricians. This equipment is designed
to operate in installations covered by NFPA 70, 1999 Edition (National Electric Code) and NFPA-75,
1992 (code for Protection of Electronic Computer/Data Processing Equipment). For electrical power
ratings on options, see the product rating label or the user documentation supplied with that option.

WARNING!

To reduce the risk of personal injury, fire, or damage to the equipment, do not overload the AC supply
branch circuit that provides power to the rack. Consult the electrical authority having jurisdiction over
wiring and installation requirements of your facility.

Installing and replacing hardware

30