5 Fiber


All Fiber Optic Standards contained herein are applicable to any manufacturer’s product that
can be administered or managed by AT&T personnel. All references to SingleMode fiber shall
be considered Bend Insensitive Fiber (BIF).

5.1 Fiber Optic Mode


Fiber Optic cards, transmitters and receivers shall be SingleMode.

5.2 Fiber Optic Cable

Fiber Optic cables/jumpers/patch cords shall adhere to Telcordia Standards as defined in GR-
409, Generic Requirements for Premises Fiber Optic Cable
and GR-326, Generic Requirements
for Singlemode Optical Connectors and Jumper assemblies.

5.3 Optical Cable/Jumpers & Connectors


Fiber Cross Connect Cables/Jumpers and Connectors shall be SingleMode.

5.4 Fiber Attenuators


Attenuators shall be SingleMode.

5.5 Fiber Connector Boots


Fiber connector boots shall be straight and not angled.

5.6 Fiber Minimum Bend Radius


The minimum fiber bend radius shall be 1inch or 10 times the cable diameter at any point
whichever is greater. Network equipment shall provide fiber management facilities that
maintain a minimum 1 inch bend radius from the connector until handoff to the bay or cabinet
fiber management facilities. See Figure 5-1

5.7 Maximum Fiber Connector length


The maximum fiber connector length (including boot) away from the mating connector housing
shall not exceed 2.25 inches. See Figure 5-1

5.8 Minimum Distance Between Connector Housing and 90 Degree Bend


Minimum Fiber distance away from a connector housing to bend 90 degrees shall be 3.75-
inches. See Figure 5–1.


Figure 5-1