Common Systems Connection Standards AT&T Services, Inc
Date: June 2013

ATT-TP-76450, Issue 15

Copyright

©

2013, AT&T . All Rights Reserved.

Page 22

6.9 Media Converter


Media converters shall be optical range extenders for the limited Electrical Ethernet signal.

6.10 Central Office Copper Wire and Cable Flammability Ratings


Wire and Cable with UL Flammability Ratings of CMX and CMU must not be used within AT&T
central offices as UL Flammability Ratings must be MP/CM(same floor), MPR/CMR(Riser-
Between Floor) or MPP/CMP(Plenum Condition).

6.11 Central Office Copper Wire and Cable


Frame Wire, DS1 Cross-Connect Wire, Switchboard Cable, Tie Cables and T1 Cable

6.12 Central Office Copper Coaxial Cable


734C/1734C, 735C/1735C Single Conductor and Multiple Conductor Coaxial Cables

6.13 Central Office Copper "Bits" Synchronous Timing Cables


1175A Red Jacketed Bits Timing Cable for all regions except Legacy AT&T, which will use gray
jacketed 1175A.

6.14 Central Office Copper Wire and Cable Minimum Inside Bend Radius


For Switchboard, Shielded and Twin Conductor Cable, 5X the Cable Diameter

6.15 Central Office Copper Coaxial Cable Minimum Inside Bend Radius


For Non-Bundled 734 or 735 Type Coaxial Cable and for Bundled 734 Type Coaxial Cable, 7X
the Cable/Bundle Diameter.

For Bundled 735 Type Coaxial Cable, 10X the Bundle Diameter.

6.16 Copper Cable Terminations


Copper Cable Terminations must have both toe and heel screw terminations for permanent
lockdown. If a 90 degree connector is used and blocks the screw, use a clamp to permanently
terminate the connector.

6.17 Cable Trays


Panels that use twisted pair jumper/cables less than 25 pair groups will be required to have a
cable tray

or rings. Do not place jumpers without a protection tray.